03. What is the recommended Seismic support spacing?


Applies To
Product(s):AutoPIPE
Version(s):ALL
Environment: N/A
Area: Seismic Load case
Original Author:Bentley Technical Support Group
Date Logged
& Current Version
Dec 2014
09.06.01.10

Problem:

What is the recommended Seismic support spacing?

Solution:

MSS SP-127-2001 (Bracing for piping Systems Seismic - Wind - Dynamic) recommends a lateral seismic support every 40ft and longitudinal support every 80ft. 

But just note this guideline tends to be conservative and over predict number and size of seismic supports.